NiCd battery Hoppecke grid | power FNC 35 H 1.2V 35Ah
Description
Hoppecke grid | power FNC
The grid | power FNC nickel-cadmium battery is based on unique fiber-structure technology. In this design, the active material is embedded within a fabric made of nickel-plated plastic fibers, creating a highly effective and stable electrochemical connection between the components. Consequently, the FNC battery withstands severe shock and vibration loads and offers a long service life and extended cycle life, even under extreme temperature conditions. Thanks to the four available performance classes—X, H, M, and L—a very wide range of stationary UPS applications can be optimally covered. Everything from high-current discharges in diesel generator applications to long-duration discharges in conventional UPS systems can be handled efficiently using the appropriate battery type.
Particularly in applications subject to extreme temperatures, grid | power FNC stands out due to its long service life, thereby reducing replacement intervals and the costs associated with a new battery system.

APPLICATIONS:
- emergency power backup (UPS)
- power stations and transformer substations
- emergency lighting
- telecommunications systems
- transport control and signaling systems (rail, road, air, etc.)
- starting electric generators or engines
- other stationary applications similar to the above (excluding large-scale storage)
ADVANTAGES:
- Excellent investment protection thanks to a long and consistently reliable service life (up to 25 years).
- Flexible use in extreme temperatures ranging from -40°C to +60°C, thanks to temperature-resistant materials.
- Simple, long-term storage capability in the event of unexpected project delays.
- The right battery for the right application, thanks to four optimized performance classes (X – engine starting and UPS; H – engine starting, UPS, and switchgear applications with discharge times up to 30 minutes; M – emergency applications with discharge times of 0.5 to 2 hours; L – applications with highly varied discharge characteristics).
TECHNICAL SPECIFICATION:
Brand/Manufacturer: HOPPECKE Batterien GmbH & Co. KG, Bontkirchener Str. 1 59929 Brilon, Germany, info@hoppecke.com
Responsible entity in the EU: HOPPECKE Batterien GmbH & Co. KG, Bontkirchener Str. 1 59929 Brilon, Germany, info@hoppecke.com
Battery range: grid | power FNC – NiCd batteries featuring unique fiber structure technology
Model: FNC 35 H
Casing: Robust, translucent polypropylene for visual electrolyte level inspection
Technology: NiCd with liquid electrolyte (density 1.19 kg/liter at +20°C)
Applications: Stationary – safety systems, UPS, telecommunications, industrial generator starting
Nominal voltage: 1.2 V
Nominal capacity: 35 Ah C5
Electrolyte volume: 0.76 liters
Operating temperature: -25... +60°C
Design life: up to 25 years, subject to correct sizing, intended use, and operating conditions
Charging voltage and current – float: 1.4...1.45V/cell, with current 0.1...0.4 x C5
Charging voltage and current – boost: 1.5...1.6V/cell, with current 0.1...0.4 x C5
Recharge time: 90% charge in under 5 hours
Dimensions: 47 x 122 x H309 mm
Approximate weight: ~2.6 kg with electrolyte / ~1.7 kg without electrolyte

Details
What customers are saying
Write a review and earn loyalty points worth RON 10.00.